Why Does the Smart-UPS Ultra Battery Cycle Between 94% and 100% State of Charge?

Issue:

The battery state of charge of certain Smart-UPS Ultra models may fluctuate between 94% and 100% during normal operation.

Product Line:

Smart-UPS Ultra 5-10kW

  • Models; SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM4UI, SRTL10KRM4UT

Smart-UPS Modular Ultra

  • All models starting with the prefix SRYL

Answer:

This behavior is normal and expected.


The UPS uses a Li-ion battery charging strategy designed to protect battery health. Once the battery reaches 100% state of charge (SoC), the charger is intentionally turned off.


During normal operation, the battery will then discharge slightly. When the SoC drops to approximately 94%, the charger automatically turns back on to recharge the battery.


As a result, the reported battery SoC may cycle between ~94% and 100%. This is part of normal operation and does not indicate a fault or defect.

Schneider Electric Sverige

Utforska mer
Produkt:
Utforska mer
Produkt:

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings