我们今天能为您提供什么帮助?

SEPAM Trip Curves: Type 1 versus Type 1.2

Issue

User would like to understand the difference in tripping characteristics between Type 1 and Type 1.2 trip curves on SEPAM relays.

Product

SEPAM Series 20
SEPAM Series 40
SEPAM Series 80

Environment

SFT2841 configuration software

Cause

Confusion arises due to the availability of two curve types (Type 1 and Type 1.2) that appear similar but have different pickup conditions, which affects protection coordination and relay response.

Resolution

SEPAM relays offer two selectable trip curve types: Type 1 and Type 1.2.

  • Type 1 Curve:
    • Pickup occurs when the measured current equals the relay threshold setting
    • Condition: I = Is
  • Type 1.2 Curve:
    • Pickup occurs when the measured current reaches 1.2 times the relay threshold setting
    • Condition: I = 1.2 × Is
    • After pickup, it follows the same tripping characteristics as the standard Type 1 (IEC) curve

Key difference:

  • The only distinction between the two curves is the pickup level
  • Once pickup is reached, both curves behave identically in terms of time-current characteristics

For further analysis and visualization:

  • Refer to the available trip curve calculators for SEPAM and MiCOM relays
  • Review the comparison charts showing Type 1 vs Type 1.2 characteristics

Type table


IDMT Curve

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings