If you are using a 3P PowerTag NSX on a 3P+N system please check that:
- you have connected the white wire to the Neutral of your panel
- the Electrical Network System is defined as 3PH4W under your Smartlink or PowerTag Link Web Interface
Опубліковано для:Schneider Electric Україна







