United Kingdom
Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all Altivar 312
Schneider Eletric ATV312H018M2B Picture

ATV312H018M2B

Schneider Eletric ATV312H018M2B Picture
ATV312H018M2B

variable speed drive ATV312 - 0.18kW - 0.6kVA - 24W - 200..240 V- 1-phase supply

Show more characteristics
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Altivar 312
    product or component type
    Variable speed drive
    product destination
    Asynchronous motors
    product specific application
    Simple machine
    assembly style
    With heat sink
    component name
    ATV312
    motor power kW
    0.18 kW
    motor power hp
    0.25 hp
    [Us] rated supply voltage
    200...240 V - 15...10 %
    supply frequency
    50...60 Hz - 5...5 %
    network number of phases
    Single phase
    line current
    2.5 A at 240 V
    3 A at 200 V, Isc = 1 kA
    EMC filter
    Integrated
    apparent power
    0.6 kVA
    maximum transient current
    2.3 A for 60 s
    power dissipation in W
    24 W at nominal load
    speed range
    1…50
    asynchronous motor control profile
    Factory set : constant torque
    Sensorless flux vector control with PWM type motor control signal
    electrical connection
    L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5 mm² AWG 14
    supply
    Internal supply for logic inputs: 19...30 V 100 mA, protection type: overload and short-circuit protection
    Internal supply for reference potentiometer (2.2 to 10 kOhm): 10...10.8 V 10 mA, protection type: overload and short-circuit protection
    communication port protocol
    Modbus
    CANopen
    IP degree of protection
    IP20 on upper part without cover plate
    IP21 on connection terminals
    IP31 on upper part
    IP41 on upper part
    option card
    Communication card for CANopen daisy chain
    Communication card for DeviceNet
    Communication card for Fipio
    Communication card for Modbus TCP
    Communication card for Profibus DP
    Complementary
    supply voltage limits
    170…264 V
    network frequency
    47.5...63 Hz
    prospective line Isc
    1 kA
    continuous output current
    1.5 A at 4 kHz
    output frequency
    0…500 kHz
    nominal switching frequency
    4 kHz
    switching frequency
    2...16 kHz adjustable
    transient overtorque
    170…200 % of nominal motor torque
    braking torque
    150 % during 60 s with braking resistor
    100 % with braking resistor continuously
    150 % without braking resistor
    regulation loop
    Frequency PI regulator
    motor slip compensation
    Suppressable
    Adjustable
    Automatic whatever the load
    output voltage
    <= power supply voltage
    tightening torque
    L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 0.8 N.m
    insulation
    Electrical between power and control
    acceleration and deceleration ramps
    Linear adjustable separately from 0.1 to 999.9 s
    S, U or customized
    braking to standstill
    By DC injection
    protection type
    Input phase breaks: drive
    Line supply overvoltage and undervoltage safety circuits: drive
    Line supply phase loss safety function, for three phases supply: drive
    Motor phase breaks: drive
    Overcurrent between output phases and earth (on power up only): drive
    Overheating protection: drive
    Short-circuit between motor phases: drive
    Thermal protection: motor
    insulation resistance
    >= 500 mOhm 500 V DC for 1 minute
    local signalling
    1 LED (red)drive voltage:
    Four 7-segment display unitsCANopen bus status:
    time constant
    5 ms for reference change
    frequency resolution
    Analog input: 0.1...100 Hz
    Display unit: 0.1 Hz
    connector type
    1 RJ45 for Modbus/CANopen
    physical interface
    RS485 multidrop serial link
    transmission frame
    RTU
    transmission rate
    10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen
    4800, 9600 or 19200 bps for Modbus
    number of addresses
    1…127 for CANopen
    1…247 for Modbus
    number of drive
    127 for CANopen
    31 for Modbus
    marking
    CE
    operating position
    Vertical +/- 10 degree
    height
    145 mm
    width
    72 mm
    depth
    132 mm
    net weight
    1.5 kg
    Environment
    dielectric strength
    2040 V DC between earth and power terminals
    2880 V AC between control and power terminals
    electromagnetic compatibility
    1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
    Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
    Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
    standards
    IEC 61800-3
    IEC 61800-5-1
    product certifications
    DNV
    UL
    NOM
    CSA
    C-Tick
    GOST
    pollution degree
    2
    protective treatment
    TC
    vibration resistance
    1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
    1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
    shock resistance
    15 gn for 11 ms conforming to EN/IEC 60068-2-27
    relative humidity
    5…95 % without condensation conforming to IEC 60068-2-3
    5…95 % without dripping water conforming to IEC 60068-2-3
    ambient air temperature for storage
    -25…70 °C
    ambient air temperature for operation
    -10…50 °C without (with protective cover on top of the drive)
    -10…60 °C with derating factor (without protective cover on top of the drive)
    operating altitude
    <= 1000 m without
    1000...2000 m with current derating 1 % per 100 m
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • All Languages15
    • English17
    • Chinese3
    Catalogue
    Format
    Size
    Date
    Add to My Documents
    Size pdf
    Size 23.3 MB
    Date 01/05/11
    User guide
    Format
    Size
    Date
    Add to My Documents
    Size pdf
    Size 1.2 MB
    Date 10/02/17
    Size pdf
    Size 1.8 MB
    Date 06/05/16
    Description
    V5.1IE57
    Size pdf
    Size 1.6 MB
    Date 29/04/16
    1) ATV312 Getting Stated Annex : SCCR (Version 04)
    Description
    Short-Circuit Current Ratings (SCCR) and branch circuit protection The table shows recommended fuse ratings for UL and CSA requirements. The components are for use together in accordance with standard UL508
    Size pdf
    Size 210.6 KB
    Date 29/04/16
    Description
    Short-Circuit Current Ratings (SCCR) and branch circuit protection The table shows recommended fuse ratings for UL and CSA requirements. The components are for use together in accordance with standard UL508
    Size pdf
    Size 2.3 MB
    Date 31/05/13
    Size pdf
    Size 2.8 MB
    Date 30/09/12
    Size pdf
    Size 1.9 MB
    Date 30/09/12
    Size pdf
    Size 2 MB
    Date 29/06/12
    Instruction sheet
    Format
    Size
    Date
    Add to My Documents
    Size pdf
    Size 389.4 KB
    Date 31/07/18
    Size pdf
    Size 675.9 KB
    Date 28/02/18
    Certificate
    Format
    Size
    Date
    Add to My Documents
    Size pdf
    Size 599.1 KB
    Date 20/04/16
    Size pdf
    Size 741.2 KB
    Date 28/02/12
    Size pdf
    Size 527.5 KB
    Date 19/04/10
    Product Environmental Profile
    Format
    Size
    Date
    Add to My Documents
    Instruction Sheet: China RoHS - Hazardous Substances Table (Version 01)
    Description
    This table is made according to SJ/T 11364. O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572
    Size pdf
    Size 1.1 MB
    Date 30/05/16
    Description
    This table is made according to SJ/T 11364. O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /