Does Square D offer 9070 Type T control transformers with multitap capabilities as a Type TF (factory installed fuse block)?

Issue:
Does Square D offer 9070 Type T control transformers with multitap capabilities as a Type TF (factory installed fuse block)?

Product Line:
Low voltage dry type transformers.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
As long as the secondary is a single output voltage (not a multitap secondary), then Square D offers the Type TF option (3 pole fuse block, 2 primary[rejection type], 1 secondary [non-rejection type]). If the transformer has a multitap secondary, then Square D offers a Type TF with a R02 option, which is primary fusing only (2 pole fuse block with 2 primary, rejection type).