How is OTR parameter (motor torque) expressed as a value via serial communication on the ATV32 drive?

Resolution:
Motor torque, OTR, is displayed by the drive as percentage of nominal motor torque as a value between 0% and 300%.
When reading motor torque over the network from register 3205, it will be displayed as a value between 0 and 8192.  0 = 0% torque, 8192 = 300% torque.   When the motor is running at nominal torque, reading parameter 3205 will return the number 2731.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: