ATV32 drive has a blank display and will not power up.

Resolution:

If the ATV32 display is blank, perform the following troubleshooting checks:

  1. Verify the input line voltage at terminals L1, L2, and L3 to confirm that power is reaching the drive.

  2. Measure the DC bus voltage between terminals PA and PC (if applicable).

    • The expected DC bus voltage is approximately: Line voltage times Square root of 2

      DC Bus Voltage = AC Line Voltage × 1.414

  3. Check the internal power supplies:

    • +10 VDC
    • +24 VDC
  4. Remove all control wiring from the drive to ensure that an external device is not loading down or shorting the internal power supplies.

How to Interpret the Results

  • Input line voltage is present, but there is no DC bus voltage:

    This condition typically indicates an internal drive failure, such as a problem in the rectifier or power section.

  • Input line voltage and DC bus voltage are both present, but either the +10 VDC or +24 VDC supply is missing:

    This is an indication of an internal drive fault. The drive may require repair or replacement.

  • The control voltages return to normal after removing the control wiring:

    An external device or wiring issue may be causing the internal power supply to collapse. Inspect the connected control circuitry before reconnecting the wiring.

If all checks have been completed and the display remains blank, the drive is likely damaged and needs to be replaced.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings