How can we help you today?
Can an ATV212 logic input be programmed as both a run command and a preset speed?
Issue:
ATV212 run activate and preset speed on the same input.
Product Line:
S-Flex ATV212
Environment:
All
Cause:
Set up Run and Preset speed at the same time.
Resolution:
Yes. The logic inputs have options for combination assignments.
22 = run forward + preset speed 1
23 = run reverse + preset speed 1
Eg: Logic input F assignment F111 = 22
Input OFF - Motor stops
Input ON - Motor runs forward at speed set by Sr1 (preset speed 1)
ATV212 run activate and preset speed on the same input.
Product Line:
S-Flex ATV212
Environment:
All
Cause:
Set up Run and Preset speed at the same time.
Resolution:
Yes. The logic inputs have options for combination assignments.
22 = run forward + preset speed 1
23 = run reverse + preset speed 1
Eg: Logic input F assignment F111 = 22
Input OFF - Motor stops
Input ON - Motor runs forward at speed set by Sr1 (preset speed 1)
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.