Is it ok for a GFI ground fault receptacle to be used downstream of a CAFI or AFI arc fault circuit breaker?
Issue:
Is it ok for a GFI ground fault receptacle to be used downstream of a CAFI or AFI arc fault circuit breaker? Will they interfere with each other?
Product Line:
Circuit Breakers
Resolution:
Yes, it is ok for a GFI receptacle to be used downstream of a CAFI or AFI arc fault circuit breaker. One does not interfere with the operation of the other.
NOTE: Depending on the situation, we suggest considering use of the DF dual function circuit breaker. This breaker combines CAFI arc fault protection with GFI ground fault protection in one breaker. This would eliminate the need for a downstream GFI receptacle.
Is it ok for a GFI ground fault receptacle to be used downstream of a CAFI or AFI arc fault circuit breaker? Will they interfere with each other?
Product Line:
Circuit Breakers
Resolution:
Yes, it is ok for a GFI receptacle to be used downstream of a CAFI or AFI arc fault circuit breaker. One does not interfere with the operation of the other.
NOTE: Depending on the situation, we suggest considering use of the DF dual function circuit breaker. This breaker combines CAFI arc fault protection with GFI ground fault protection in one breaker. This would eliminate the need for a downstream GFI receptacle.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.