Sepam is showing a reverse rotation Alarm.
Issue
On the front display of the Sepam it is showing a reverse rotation Alarm.
Product Line
Sepam Series 40
Sepam Series 80
Cause
The Sepam is looking at the voltage phase rotation. On the Sepam 40s it is looking for an ABC rotation. The Sepam 80s it can be wired ABC or ACB.
Resolution
Sepam 40:
The only way to fix the reverse rotation alarm is to re-wire the voltages to an ABC rotation even if its a ACB rotation. To help on the wiring please click here for the Sepam 40 wiring diagram.
Sepam 80:
One can just make the changes in SFT2841 by going to the General characteristics tab. In the Electrical network box look for Phase rotation direction and select which rotation is needed.

On the front display of the Sepam it is showing a reverse rotation Alarm.
Product Line
Sepam Series 40
Sepam Series 80
Cause
The Sepam is looking at the voltage phase rotation. On the Sepam 40s it is looking for an ABC rotation. The Sepam 80s it can be wired ABC or ACB.
Resolution
Sepam 40:
The only way to fix the reverse rotation alarm is to re-wire the voltages to an ABC rotation even if its a ACB rotation. To help on the wiring please click here for the Sepam 40 wiring diagram.
Sepam 80:
One can just make the changes in SFT2841 by going to the General characteristics tab. In the Electrical network box look for Phase rotation direction and select which rotation is needed.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.