How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge?
Issue:
How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge.
Product Line:
174CEV20040 Modbus Plus to Ethernet Bridge
Environment:
Monitor Console Mode (local access to the bridge).
This product was discontinued on 9/24.
Cause:
The 174CEV20040 Modbus Plus to Ethernet Bridge didn’t have the correct time but the user didn’t know how to set it up
Resolution:
To change the Time and Date on a 174CEV20040 bridge, the procedure must be performed using the Monitor Console Mode.
- Connect a standard PC keyboard, mouse, and VGA monitor directly to the bridge connectors.
- Power on the bridge and access the Monitor Console screen.
- Initially, all controls are grayed out and the data fields are read‑only.
- Under Administrator Account, select Login and enter the administrator password.
- The default password is password.
- Once logged in, the controls become active and Login changes to Logout.
- In the Troubleshooting Tools section, open the drop‑down menu and scroll to Time and Date, then select Run.
- In the Time and Date properties window, update the required values and select OK to save the changes.
Note: After all changes have been made press the Reboot button for the system to reboot and all changes to take effect.
เผยแพร่สำหรับ: ชไนเดอร์ อิเล็คทริค Thailand
ต้องการความช่วยเหลือใช่หรือไม่
โปรแกรมช่วยเลือกผลิตภัณฑ์
ค้นหาผลิตภัณฑ์และอุปกรณ์เสริมที่เหมาะสมกับการใช้งานของคุณได้อย่างรวดเร็วและง่ายดาย
ติดต่อฝ่ายขาย
ติดต่อสอบถามเกี่ยวกับการขายผ่านทางเว็บไซต์ และผู้เชี่ยวชาญจะติดต่อกลับ
สถานที่จัดจำหน่ายอยู่ที่ใด
ค้นหาตัวแทนจำหน่าย ชไนเดอร์ อิเล็คทริค ที่ใกล้ตัวคุณที่สุดได้อย่างง่ายดาย
ศูนย์ความช่วยเหลือ
ค้นหาแหล่งข้อมูลเพื่อสนับสนุนความต้องการทั้งหมดของคุณได้จากที่เดียว