แบรนด์ของเรา

Impact-Company-Logo-English Black-01-177x54

ยินดีต้อนรับสู่เว็บไซต์ชไนเดอร์ อิเล็คทริค

ยินดีต้อนรับสู่เว็บไซต์ของเรา
		
วันนี้เราสามารถช่วยคุณได้อย่างไร?
PME 7.2.x or PME 8.0 installer fails on step "Verify databases"
Issue
When upgrading SPM 7.0.1 to PME 7.2.2 or PME 8.0...the installer fails on step "Verify Databases" with the message "The ION_Network table was not upgraded" or "An error has occurred during the ION_Network database deployment"
When opening the ION_Network.log ( located in the <install directory>\diagnostic folder), at the bottom of the file the error message reads:
"You do not have permission to use the bulk load statement"

Product Line
PME 7.2.2
PME 8.0

Environment
Upgrade to PME 7.2.2 from SPM 7.0.1
Upgrade to PME 8.0 from PME 7.2.2

Cause
The "ION" sql account does not have "sysadmin" privileges

Resolution
To provide sysadmin privileges to the "ION" Sql account, follow the below steps:
1. Open SQL Server Management Studio and log in to the instance of SQL being used by PME 7.2.x or PME 8.0, using the appropriate administrator credentials.

SQL Login

2. Expand the instance of SQL being used and the folder "security" followed by the folder "Logins"

SQL Server Login

3. Right click on the user "ION" and select "properties"
4. Click on the tab "server roles" and select the checkbox for "sysadmin"
5. Click "ok" on the login properties window and rerun the installer.

ชไนเดอร์ อิเล็คทริค Thailand

ดูข้อมูลเพิ่มเติม
รุ่น:
ดูข้อมูลเพิ่มเติม
รุ่น:
  • คู่มือผลิตภัณฑ์
  • ดาวน์โหลดซอฟต์แวร์
  • โปรแกรมช่วยเลือกผลิตภัณฑ์
  • ผลิตภัณฑ์ทดแทนและอะไหล่
  • ศูนย์ช่วยเหลือและการติดต่อ
  • ค้นหาสํานักงานของเรา
  • รับใบเสนอราคา
  • สถานที่จัดจำหน่าย
  • ชุมชน Schneider Electric
  • ร่วมงานกับเรา
  • ข้อมูลบริษัท
  • ร้องเรียนการประพฤติมิชอบ
  • การช่วยการเข้าถึง
  • ห้องข่าว
  • นักลงทุน
  • EcoStruxure
  • ค้นหาตำแหน่งงาน
  • บล็อก
  • นโยบายความเป็นส่วนตัว
  • ประกาศเกี่ยวกับคุกกี้
  • ข้อกำหนดการใช้งาน
  • Change your cookie settings