Does the ATV660 with Full Voltage Bypass have solid state overload protection when in the bypass?

Issue:
Does the Enclosed ATV660 when ordered with Bypass have Solid State Overload?

Product Line:
Altivar and Altivar Process Drive

Environment:
Altivar, Process Drive, ATV660 Enclosed AC Drive

Resolution:
Per the manual, linked below, the ATV660 if ordered with Full Voltage Bypass uses 2 Interlinked TeSys F Contactors, for switching between Drive (AFC) or Bypass (BYP) Mode, which are not Solid State. Also included is a Class 20 separate Overload, as shown on page 43-EN. Please don't hesitate to reply if you have any further questions.

Included with Bypass
• Class 20 overload protection
• Overload Trip (yellow) and Bypass (yellow) pilot lights
• Bypass and isolation contactors with mechanical and electrical interlocking
• Bypass and isolation contactor sequencing provides true motor isolation

ATV660 Manual - https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=NHA91297_02.pdf&p_Doc_Ref=NHA91297

ชไนเดอร์ อิเล็คทริค Thailand

ดูข้อมูลเพิ่มเติม
รุ่น:
ดูข้อมูลเพิ่มเติม
รุ่น:
  • คู่มือผลิตภัณฑ์
  • ดาวน์โหลดซอฟต์แวร์
  • โปรแกรมช่วยเลือกผลิตภัณฑ์
  • ผลิตภัณฑ์ทดแทนและอะไหล่
  • ศูนย์ช่วยเหลือและการติดต่อ
  • ค้นหาสํานักงานของเรา
  • รับใบเสนอราคา
  • สถานที่จัดจำหน่าย
  • ชุมชน Schneider Electric
  • ร่วมงานกับเรา
  • ข้อมูลบริษัท
  • ร้องเรียนการประพฤติมิชอบ
  • การช่วยการเข้าถึง
  • ห้องข่าว
  • นักลงทุน
  • EcoStruxure
  • ค้นหาตำแหน่งงาน
  • บล็อก
  • นโยบายความเป็นส่วนตัว
  • ประกาศเกี่ยวกับคุกกี้
  • ข้อกำหนดการใช้งาน
  • Change your cookie settings