How do I turn on the Multi-Pump function on the Altivar 630 Process drive?
Resolution:
Turn on Macro Configuration to either (Booster Control or Level Control)
[Complete settings] >> [Macro configuration]
[Complete settings] >> [Pump functions] >> [Booster control] >> [System architecture]
[Pump System Architecture] MPSA would have to be turn on or set to [Single Drive] VNDOL or [Multi Drive]
Firmware version up to 1.5 will give you choice of Single Drive only. Version 1.6 and over will give you choice of Single and Multi Drive.
Once [Pump System Architecture] MPSA has been configured then configure [Nb Of Pumps] MPPN
(max. 6 pumps)
To configure each individual pumps,
[Complete settings] [Pump functions] [Booster control] [System architecture] [Pumps
configuration]
See the attached document for additional programming assistance.