How can we help you today?

What is the Product Restart function on the Altivar Process Drive?

Product Restart is a reset of drive micro-controller. This is "equivalent" to a drive physical power OFF/ON. When Product restart is activated, the drive reboots.
This function can be used to reset an error that normally requires a drive power cycle. Instead, you use the product restart assignment function, and the drive will reboot and clear the fault (only if root cause of the error has been corrected).

To program
Set Access Level to Expert - [My Preferences] [Access Level]
Go to
[Complete settings] [Error/Warning handling] [Fault reset]
[Product Restart] rP
[Prod Restart Assign] rPA

But keep in mind that changing Product Restart to YES  and  using a digital input to trigger a Product Restart are performing the same function:
Product Reboot.

  • RP: via parameter in keypad
  • RPA: via logical input.

Using Communications
Product Restart Assignment (RPA) is the same function but can only be commanded by logic input. It cannot be commanded via Communications
If you need to do a product restart via communication, the trick is to write to the RP parameter (Logic Address - 7128).
Via communication, you write the RP parameter equal to 1, and the drive will make a product restart.

Address 7128 can NOT be entered in the Ethernet scanner tables in the drive.  This parameter is marked as R/WS indicating it can only be written to when the drive is stopped.  If it is entered into the scanner table it will force the drive into an nSt (freewheel stop) condition and prevent operation (this is true of any R/WS parameter).

Using SoMove
It is possible to initiate a Reset when connected to the drive with SoMove by selecting Device and then Restart Device.
screenshot
During the restart process the connection to the drive will be lost.

************

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.