How can we help you today?
What is the External Error (EPF1) fault on the Altivar Process Drive?
Resolution:
Probable Cause
- Event triggered by an external device, depending on user.
- An external error has been triggered via Embedded Ethernet
Remedy
- Check External Fault settings
- [Complete settings] -> [Error/Warning handling] -> [External error]
- External error assignment. If the assigned bit state is:
- 0: there is no external error.
- 1: there is an external error (EPF1)
- Check Embedded Ethernet settings
- [Communication] -> [Comm parameters] -> [Embd Eth Config]
- A faulty or duplicate address can cause conflicting issues.
- Try setting a different fixed IP address
- Check Network or PLC settings for any other conflicts
- Check for any possible electrical interferences
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.