How do you setup the PID sleep wake up function on the ATV630 process drive?

Published date: 15 May 2020

Issue:
ATV630 sleep wake up function using the PID setup

Product Line:
Altivar ATV630 and ATV930 drive

Environment:
All 

Cause:
setup sleep and wake up function.

Resolution:
Pump Functions main menu:
PID controller Menu
PID wake up and sleep function on the ATV630 Process drive. 
PID has to be activated and ON. 
Low speed has to be set to a value above 0 or 30hz as an example.
PID min output has to match your low speed or 30hz.

Pump Functions menu
Sleep/Wake up enter

Sleep setup example:
-Sleep detect mode = speed
-sleep min speed= 31 (needs to be 1hz higher than your low speed very important)
-Sleep delay= 3 seconds
Wake up Setup example:
-Wake up Menu (2nd Tab)
-Wake up mode= Error or Feedback.  Set to Error on this example
-Wake up Process Error= 3-5% will wake the drive back up. 