Issue:
24VDC on DI1 with no wires connected on ATV340.
Product Line:
Altivar 340
Environment:
All
Cause:
Installation
Resolution:
Check the position of the SK/EXT/SRC dip switch. The switch should be set to the SRC position if you want to activate the drive's digital inputs by supplying 24VDC to them.
See the ATV340 Installation Manual, pages 104 and 105 for details on this switch:
https://www.se.com/ww/en/download/document/NVE61069/
24VDC on DI1 with no wires connected on ATV340.
Product Line:
Altivar 340
Environment:
All
Cause:
Installation
Resolution:
Check the position of the SK/EXT/SRC dip switch. The switch should be set to the SRC position if you want to activate the drive's digital inputs by supplying 24VDC to them.
See the ATV340 Installation Manual, pages 104 and 105 for details on this switch:
https://www.se.com/ww/en/download/document/NVE61069/