Importing a '.cid file for a third party device returns the error 'Invalid File''
Issue
Importing a '.cid file for a third party device returns the error 'Invalid File''
Product Line
BMENOP0300
Environment
Unity, Windows 10
Resolution
Attempts to import a '.cid' file for a third (e.g., ABB, etc.) into the 'IEC 61850 Configuration Tool' returns the error 'Invalid file. the file content is invalid'.
This issue is the result of an error within the '.cid' file. Additional information about the error can be found by saving and reviewing the log file:
e.g.,
Importing a '.cid file for a third party device returns the error 'Invalid File''
Product Line
BMENOP0300
Environment
Unity, Windows 10
Resolution
Attempts to import a '.cid' file for a third (e.g., ABB, etc.) into the 'IEC 61850 Configuration Tool' returns the error 'Invalid file. the file content is invalid'.
This issue is the result of an error within the '.cid' file. Additional information about the error can be found by saving and reviewing the log file:
e.g.,
Node: P | Line Number: 330 | Line Position: 74,The 'http://www.iec.ch/61850/2003/SCL:P' element is invalid -
The value '1,3,9999,23' is invalid according to its datatype 'http://www.iec.ch/61850/2003/SCL:tP_OSI-AP-Title' - The
Pattern constraint failed.'
To see where in the '.cid'the error is located, Wordpad can be used to to search for the invalid value:Searching the web can also help find reasons for the issue: e.g.,
To resolve the issue, contact the third party manufacture for a corrected '.cid' file.
เผยแพร่สำหรับ: ชไนเดอร์ อิเล็คทริค Thailand


ต้องการความช่วยเหลือใช่หรือไม่
โปรแกรมช่วยเลือกผลิตภัณฑ์
ค้นหาผลิตภัณฑ์และอุปกรณ์เสริมที่เหมาะสมกับการใช้งานของคุณได้อย่างรวดเร็วและง่ายดาย
ติดต่อฝ่ายขาย
ติดต่อสอบถามเกี่ยวกับการขายผ่านทางเว็บไซต์ และผู้เชี่ยวชาญจะติดต่อกลับ
สถานที่จัดจำหน่ายอยู่ที่ใด
ค้นหาตัวแทนจำหน่าย ชไนเดอร์ อิเล็คทริค ที่ใกล้ตัวคุณที่สุดได้อย่างง่ายดาย
ศูนย์ความช่วยเหลือ
ค้นหาแหล่งข้อมูลเพื่อสนับสนุนความต้องการทั้งหมดของคุณได้จากที่เดียว