{}

Impact-Company-Logo-English Black-01-177x54
Share Price 
Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs

What causes an ATV320 to display an OBF fault?

Article available in these languages: Czech, Japanese

Issue:
OBF fault on a ATV320

Product Line:
Altivar 320

Environment:
All

Cause:
OBF fault on drive display

Resolution:
Possible causes:
• Braking too sudden or driving load.
• Supply voltage too high.

Remedies:
• Increase the deceleration time.
• Install a braking resistor if necessary.
• Activate the [Dec ramp adapt.] (brA) function page 172, if it is compatible with the application.
• Check the supply voltage.

Schneider Electric Global

Explore more
Explore more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.