What type of GSM/GPRS service are required for the FactoryCast Gateways (TSXETG302x) SIM card?

Issue:

Identify what type of GSM/GPRS cellular service is required for SIM cards used with FactoryCast Gateways TSXETG302x for reliable remote access and routing.

Product Line:

TSXETG3021

TSXETG3022

Environment:

FactoryCast HMI Gateway deployed over GSM/GPRS (2G) using a carrier SIM for remote monitoring/control and Modbus/Ethernet routing services.

Cause:

Cellular carriers offer M2M (Machine‑to‑Machine)-oriented GSM/GPRS subscriptions that differ by:

  • Data plan sizing (billing by MB/month).
  • IP addressing (Static vs Dynamic).
  • Inbound TCP port policy (some plans block ports—often <1024—for security). If inbound ports are blocked, remote connections to the gateway can be constrained.
  • Regional availability note: TSXETG302x relies on 2G (GSM/GPRS). Many operators have sunset plans or have already retired 2G/3G, varying by country and carrier—verify coverage where you deploy.

Resolution:

Choose an M2M GSM/GPRS subscription that supports the gateway’s remote access needs:

  1. Public APN + Public IP: Prefer plans that provide a public APN with a public, Internet‑reachable IP for the SIM.
  2. Static IP: Use a static IP to simplify fixed inbound access, firewall rules, and diagnostics.
  3. No inbound TCP blocks: Select plans where incoming TCP ports are not blocked, so routing services on the TSXETG302x are fully usable.
  4. Size the data plan: Match the plan’s monthly data allowance to your expected traffic.
  5. Confirm 2G support: Before ordering SIMs, confirm local 2G (GSM/GPRS) is still active with your target MNO(s); if sunset is imminent, consider alternate connectivity paths.

Schneider Electric Global

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Our Mission
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Financial Results
  • Annual Reports
  • Share Price
  • Investor Events
  • Sustainability
  • New Energy Landscape
  • Next-generation Automation
  • AI and Technology
  • Reports
  • Foundation
  • Consulting
  • Help Center
  • Solutions
  • Software
  • Blog
  • General Terms of Business
  • Global - FR
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings