What is the replacement coil for the electrically held 8903L lighting contactor?

Published date: 25 October 2019

Issue:
Replacement coils for 8903 Type L contactor: 

Product Line:
8903 type L Lighting contactors

Environment:
North American Product

Cause: 
Maintenance 

Resolution:
This depends on pole quantity and voltage:
2-6 poles, 9998L**
7-12 poles, 9998LH**
 
 Poles Coil Class and Type  HZ Suffix Number
(complete coil number consists of the class and type followed by the suffix)
Coil VA
 24v  110-115v  120v  208v  220v  240v  277v  380v  440v  480v  550v  600v  Inrush  Sealed
2-6 9998L  60 23 - 44 50 [*] 53 55 - - 62 - 65 150 30
50 24 44 45 52 53 54 - 60 62 63 65 66 140 30
8-12  9998LH 60 23 - 44 50 [*] 53 55 - - 62 - 65 180 35
50 24 44 45 - 53 54 - 60 62 - 65 - 170 35

* - use a 60 Hz coil of the next higher voltage