{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
Can EPO Circuits be Wired in Parallel?

No.  The EPO circuit on each UPS has a surge suppression element . By paralleling these circuits the results may cause the UPS to EPO themselves and each other. Independant poles of an EPO (single action, multi-pole) switch must be run to each UPS.



Schneider Electric Global

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.