Issue:
ATS48 Fan Specification
Product Line:
Altistart 48
Environment:
All
Cause:
NA
Resolution:
ATS48D17Y and ATS48D22Y do not have fans. All other models do have fans.
The fans will operate when the heatsink temperature is greater than 50C.
The fans will stop operating when the heatsink temperature drops below 40C.
ATS48 Fan Specification
Product Line:
Altistart 48
Environment:
All
Cause:
NA
Resolution:
ATS48D17Y and ATS48D22Y do not have fans. All other models do have fans.
The fans will operate when the heatsink temperature is greater than 50C.
The fans will stop operating when the heatsink temperature drops below 40C.
Released for:Schneider Electric Global

