Issue:
Wiring up a 2-wire or 3-wire transducer to the S-Flex 212 Drive.
Product Line:
S-Flex 212 and 21
Environment:
All
Cause:
Needs to wire in a 3 wire 4-20mA transducer to the S-Flex 212 drive.
Resolution:
3 wire transducer:
P24
VIA (4-20mA)
CC
2 wire transducer:
P24
VIA (4-20mA)
Released for:Schneider Electric Global

