{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
What is the meaning of the error code 'FFFF' on the READ_REG_QX Function Block Status pin?

This error code is not documented but indicates that the Quantum 140CRP31200 module does not have a minimum firmware version of 1.56. For BMXCRA31210 with BMXNOM0200 communications on a QEIO network, the Quantum 140CRP31200 module requires at least the firmware version of 1.56.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: