Why is my 140NOA61110 showing an Error Code E04?

Issue

Why is my 140NOA61110 showing an error code E04?

Product Line

INTERBUS

Environment

140NOA61110

Resolution

This error code indicates that the master read its configuration but when it tried to verify the real world configuration, no devices replied. This typically indicates no network connected to the master, or cabling issues.