Wiring a 2-wire Transmitter to an STBACI1400 Analog Input

Issue
This resolution describes how to wire 2-wire analog transmitters to the inputs of an STBACI1400 analog input module.


Product Line
Advantys STB
STBACI1400


Environment


Resolution
2-wire analog transmitters require a loop power supply to power the loop. The following diagram shows how this is done with a single power supply for all current loops.