{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
Is there a Ethernet/IP module available for the Premium PLC line?

Yes. The Premium modules TSXETC100 and TSXETC101 can communicate with Ethernet/IP devices.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: