Issue
When opening different Control Expert Tools such as the Hardware Catalog Manager or Types Library Update tool they return an error.
Product line
Unity Pro
Resolution
Using the Regedit browser, access and modify the following parameter:
HKEY_LOCAL_MACHINE\wow6432node\SOFTWARE\Schneider Electric\COMMON\ObjectStoreParam then double click on AddressingSpaceSize
The default value is 0x28000000.
Modify this value to 0x18000000
When opening different Control Expert Tools such as the Hardware Catalog Manager or Types Library Update tool they return an error.
Product line
Unity Pro
Resolution
Using the Regedit browser, access and modify the following parameter:
HKEY_LOCAL_MACHINE\wow6432node\SOFTWARE\Schneider Electric\COMMON\ObjectStoreParam then double click on AddressingSpaceSize
The default value is 0x28000000.
Modify this value to 0x18000000
Released for:Schneider Electric Global

