Search FAQs
Error while generating web report: The Sort expression for the table 'shiftDescriptionTable' contains an error: Conversion from string "12:00 a.m." to type 'Date' is not valid.

Goals and Symptoms

Generating any web report will result in the following error being generated:
An error had occurred during report processing.
The Sort expression for the table 'shiftDescriptionTable' contains an error: Conversion from string "12:00 a.m." to type 'Date' is not valid.

  • The time format configured in the regional and language settings is using the AM and PM format
  • Reboot after applying settings does not help
  • Data being displayed in Vista is using this format as well

Facts and Changes

Errors like the follow may be present in the EventException table in the ION_SystemLog database:
System.ApplicationException: Error creating SQL Agent heartbeat. ---> Microsoft.SqlServer.Management.Smo.FailedOperationException: Drop failed for Job '[ION SUBSCRIPTION] - Heartbeat'. ---> Microsoft.SqlServer.Management.Common.ExecutionFailureException: An exception occurred while executing a Transact-SQL statement or batch. ---> System.Data.SqlClient.SqlException: Cannot perform this operation while SQLServerAgent is starting. Try again later. at System.Data.SqlClient.SqlConnection.OnError(SqlException exception, Boolean breakConnection) at System.Data.SqlClient.SqlInternalConnection.OnError(SqlException exception, Boolean breakConnection) at System.Data.SqlClient.TdsParser.ThrowExceptionAndWarning(TdsParserStateObject stateObj) at System.Data.SqlClient.TdsParser.Run(RunBehavior runBehavior, SqlCommand cmdHandler, SqlDataReader dataStream, BulkCopySimpleResultSet bulkCopyHandler, TdsParserStateObject stateObj) at System.Data.SqlClient.SqlCommand.RunExecuteNonQueryTds(String methodName, Boolean async) at System.Data.SqlClient.SqlCommand.InternalExecuteNonQuery(DbAsyncResult result, String methodName, Boolean sendToPipe) at System.Data.SqlClient.SqlCommand.ExecuteNonQuery() at Microsoft.SqlServer.Management.Common.ServerConnection.ExecuteNonQuery(String sqlCommand, ExecutionTypes executionType) --- End of inner exception stack trace --- at Microsoft.SqlServer.Management.Common.ServerConnection.ExecuteNonQuery(String sqlCommand, ExecutionTypes executionType) at Microsoft.SqlServer.Management.Common.ServerConnection.ExecuteNonQuery(StringCollection sqlCommands, ExecutionTypes executionType) at Microsoft.SqlServer.Management.Smo.ExecutionManager.ExecuteNonQuery(StringCollection queries) at Microsoft.SqlServer.Management.Smo.SqlSmoObject.ExecuteNonQuery(StringCollection queries, Boolean includeDbContext) at Microsoft.SqlServer.Management.Smo.SqlSmoObject.DropImplWorker(Urn& urn) at Microsoft.SqlServer.Management.Smo.SqlSmoObject.DropImpl() --- End of inner exception stack trace --- at Microsoft.SqlServer.Management.Smo.SqlSmoObject.DropImpl() at Microsoft.SqlServer.Management.Smo.Agent.Job.Drop() at PowerMeasurement.Scheduling.SQLAgentScheduler.CreateSQLAgentHeartbeat() at PowerMeasurement.Apps.Services.ReportSubscriptionService.SetupSQLAgentHeartbeat() --- End of inner exception stack trace --- at PowerMeasurement.Apps.Services.ReportSubscriptionService.SetupSQLAgentHeartbeat() at PowerMeasurement.Apps.Services.ReportSubscriptionService.OnStart(String[] args)

Causes and Fixes

The browser version of Internet Explorer is not supported. Version 6 or older is installed. Upgrade to Internet Explorer version 7 or newer and this should resolve this particular issue.


Legacy KB System (APS) Data: RESL201975 V1.0, Originally authored by DaMi on 04/15/2010, Last Edited by DaMi on 04/15/2010
Related ranges: ION Enterprise V6.0

Schneider Electric Global

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Our Mission
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Financial Results
  • Annual Reports
  • Share Price
  • Investor Events
  • Careers
  • Sustainability
  • Electricity 4.0
  • Next-generation Automation
  • AI and Technology
  • Reports
  • Foundation
  • Consulting
  • Global - FR
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings