How to setup and connect a 3720 ACM with ethernet option in ION Enterprise v6.0 Management Console.

1) Add a new ethernet device to the Management Console and add the group, name, device type, and IP Address like normal.
2) On the same ethernet device configuration page right click in the white area (below the description field) and select Advanced Properties.
3) Change the TCP/IP Port to 3720 ACM with MPE|3721 which should be an option in the drop down menu.
4) Click OK to finish