Peer Cop Limitations:
- The total number of internal words configured within the node must not exceed 500 words for specific input and 500 words specific output (i.e. 1000 words Total).
- These blocks of words should be contiguous registers.
- Up to 32 input and 32 output words per node address on the local bus.
Legacy KB System (APS) Data: RESL170484 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon Premium
Released for:Schneider Electric Global



