How do you include the initial values with a download in Unity Pro for a Premium PLC?

Product Line
Unity Pro, Premium

Resolution

To include the initial register values for a Unity Premium PLC with a download, the "Initialize %MWi on cold start" needs to be checked off under the processor configuration. To get to the configuration screen double-click on the processor under the project browser. The configuration screen will come up. Under the configuration tab there is a window called Operating Modes with five check boxes. Check off the "Initialize %MWi on cold start".