How can I check the logic inputs are working on an ATV312 drive?
Issue:
Customer is not sure if the inputs are working.  Drive is not running.

Product line:
Altivar 312, ATV312

Environment:
all

Cause:
n/a

Resolution:
Go under the SUP menu to LIA-.  Under LIA-, select parameter LIS (not LI5A).  This will show the Logic inputs from LI1 to LI6.  The dash mark will be high (closed) or Low (open).  See the attached page from the programming manual, BBV46385 as reference.

Schneider Electric Global

Attachment(s)
BBV46385_03 ATV312 IO Map.pdf [21.5 KB]
How can I check the logic inputs are working on an ATV312 drive?
Issue:
Customer is not sure if the inputs are working.  Drive is not running.

Product line:
Altivar 312, ATV312

Environment:
all

Cause:
n/a

Resolution:
Go under the SUP menu to LIA-.  Under LIA-, select parameter LIS (not LI5A).  This will show the Logic inputs from LI1 to LI6.  The dash mark will be high (closed) or Low (open).  See the attached page from the programming manual, BBV46385 as reference.
 

Schneider Electric Global

Attachment(s)
BBV46385_03 ATV312 IO Map.pdf [21.5 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.