undefined undefined
{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
MiCOM Px4x Power and/or Reactive Power showing incorrect sign
Issue
When monitoring power (kW) or reactive power (kVAR) on a MiCOM Px4x, the sign is negative when positive is expected or vice versa. Wiring has been confirmed to be correct and readings are showing correctly otherwise.

Product Line
MiCOM Px4x

Environment
MiCOM S1 Studio and front panel

Cause
The measurement mode setting is set incorrectly.

Resolution
The measurement mode default setting for a relay, and the setting that would apply to most customers, is 0. However the chart below shows other settings that are available for configuring the relay.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: