Issue:
Looking for some of the behaviors of the HMIG5U/HMIG5U2 as the temperature goes beyond the suggested operating temperatures.
Product Line:
HMIG5U, HMIG5U2
Resolution:
The HMIG5U has a maximum operating environment temperature of 60 degrees Celcius.
When the HMIG5U is used in an operating environment temperature greater than what it is rated for, the following occurs:
at 65 degrees Celcius, the screen brightness becomes a little dark
at 70 degrees Celcius, the screen brightness becomes even more dark
at 75 degrees Celcius, the screen brightness is completely dark
at 80 degrees Celcius, thermal shutdown occurs.
Looking for some of the behaviors of the HMIG5U/HMIG5U2 as the temperature goes beyond the suggested operating temperatures.
Product Line:
HMIG5U, HMIG5U2
Resolution:
The HMIG5U has a maximum operating environment temperature of 60 degrees Celcius.
When the HMIG5U is used in an operating environment temperature greater than what it is rated for, the following occurs:
at 65 degrees Celcius, the screen brightness becomes a little dark
at 70 degrees Celcius, the screen brightness becomes even more dark
at 75 degrees Celcius, the screen brightness is completely dark
at 80 degrees Celcius, thermal shutdown occurs.
Released for:Schneider Electric Global





