Issue
While using M340 extension rack and cables, Is the maximum distance between racks is 12 m while the total cumulative length is 30m?
Product Line
M340, Premium
Issue
The documentation "35012676_K01000-02.pdf" is not ambiguous:
If a customer use only 2 racks, he can realize a custom cable, but with a maximal length of 30 meters.
While using M340 extension rack and cables, Is the maximum distance between racks is 12 m while the total cumulative length is 30m?
Product Line
M340, Premium
Issue
The documentation "35012676_K01000-02.pdf" is not ambiguous:
- 4 racks maximum
- Maximum length of 30 meters (this is the maximum cumulative length between the racks)
If a customer use only 2 racks, he can realize a custom cable, but with a maximal length of 30 meters.
Released for:Schneider Electric Global