What is the minimum value braking resistor that can be used with the ATV320 series drives?

Published date: 02 January 2020

Issue:
Minimum value of the braking resistor that can be used with the ATV320 series drives.

Product Line:
ATV320 series drives

Environment:
The ATV320 series drives listed below

Cause:
Information unavailable in current literature.

Resolution:



 
Drive min resistor ohms
ATV320U02M2B 40
ATV320U04M2B 40
ATV320U06M2B 40
ATV320U07M2B 40
ATV320U11M2B 27
ATV320U15M2B 27
ATV320U22M2B 25
ATV320U02M2C 40
ATV320U04M2C 40
ATV320U06M2C 40
ATV320U07M2C 40
ATV320U11M2C 27
ATV320U15M2C 27
ATV320U22M2C 25
ATV320U02M3C 40
ATV320U04M3C 40
ATV320U06M3C 40
ATV320U07M3C 40
ATV320U11M3C 27
ATV320U15M3C 27
ATV320U22M3C 25
ATV320U30M3C 16
ATV320U40M3C 16
ATV320U55M3C 8
ATV320U75M3C 8
ATV320D11M3C 5
ATV320D15M3C 5
ATV320U04N4B 80
ATV320U06N4B 80
ATV320U07N4B 80
ATV320U11N4B 54
ATV320U15N4B 54
ATV320U22N4B 54
ATV320U30N4B 54
ATV320U40N4B 36
ATV320U04N4C 80
ATV320U06N4C 80
ATV320U07N4C 80
ATV320U11N4C 54
ATV320U15N4C 54
ATV320U22N4C 54
ATV320U30N4C 54
ATV320U40N4C 36
ATV320U55N4B 27
ATV320U75N4B 27
ATV320D11N4B 16
ATV320D15N4B 16