Issue:
On the ATV212 series drive, "Output power" is displayed as a percentage. What is the reference for this scale?
Product Line:
ATV212 series drives
Environment:
All models, All serial numbers.
Cause:
Information unavailable in current literature.
Resolution:
The Output Power percentage, as read over the network, is a percentage of the rating of the drive itself, not the motor.
On the ATV212 series drive, "Output power" is displayed as a percentage. What is the reference for this scale?
Product Line:
ATV212 series drives
Environment:
All models, All serial numbers.
Cause:
Information unavailable in current literature.
Resolution:
The Output Power percentage, as read over the network, is a percentage of the rating of the drive itself, not the motor.
Released for:Schneider Electric Global