How do you set up the reference template on the ATV320 drive for pedestal mode?

Published date: 17 January 2020

Issue:
How do you go about setting up the reference template on the ATV320 drive for pedestal mode?

Product Line:
ATV32 and ATV320

Environment:
All 

Cause:
C ustomer wants to have his 4-20mA reference signal follow 0 to 60hz even with a low speed setting on the drive of 10hz. 

Resolution:
Programming 
I/O Menu 
BSP= Reference template enter
Change to bLS= Pedestal mode.
Done