{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
ATV312 drive with a remote speed pot is working in reverse?
Issue:
Reversed remote speed pot on an ATV312 drive.

Product Line:
ATV312

Environment:
All serial numbers

Cause:
Potentiometer is working backwards

Resolution:
Swap the  +10vdc and the com terminal wires on the potentiometer to reverse the potentiometer operating direction.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: