Where do you wire in the DB resistor on the ATV320 drive?

Published date: 02 January 2020

Issue:
Wanting to wire in the DB resistor, on the ATV320 drive.

Product Line:
ATV320 with C and B suffix 

Environment:
All 

Cause:
Wiring terminations for adding a DB resistor on the ATV320 drive. 

Resolution:
The ATV320.....B   DB resistor terminals are PBe and PB.

The ATV320.....C   DB resistor terminals are PO and PB.

See the attached documents on terminations and min resistance. 


 