What is an internal serial link fault (INF3) on an ATV320 drive?

Published date: 13 February 2020

Issue:
Getting an internal serial link fault (INF3) on an ATV320 dirve.

Product Line:
Altivar 320

Environment:
All

Cause:
Communication interruption between internal cards of VFD

Resolution:
Check internal connections.  
If there is an option card, remove and re install.
Power cycle the VFD.  
Factory reset if needed.
Power up with no option card if instaled (this will perform factory reset)