How can the Altistart ATS48 soft stater be wired up for the 2 wire run control to start the motor?

Published date: 07 February 2019

Issue:
How can the Altistart ATS48 soft stater be wired up for two wire run control to start the motor?

Product Line:
Altistart ATS48 

Environment:
All 

Cause:
Basic two wire control

Resolution:
Wire the soft starters supplied +24vdc through your dry maintained contact back to the soft starters run and stop terminals. 

See the ATS48 user manual for the terminal block connections. 
https://www.se.com/us/en/download/document/1494409/


 