AS-P in version 1.9.4 can not respond for request which contain group of consecutive registers.
Exception Response FC03 - Illegal Data Address (Read Holding Register) - 00 00 00 00 00 06 FF 03 03 84 00 06 - 00 00 00 00 00 03 FF 83 02
(In this case client ask for 6 registers starting with register number 900)
Possible overwork:
1. Set HMI STU communication optimization mode to : Prefered Frame lenght = Minimum possible. Vijeo Designer, Equipment configuration.
2. Upgrade AS-P to version 2.0.3.45 (solution tested in ModScan32 tool)
Exception Response FC03 - Illegal Data Address (Read Holding Register) - 00 00 00 00 00 06 FF 03 03 84 00 06 - 00 00 00 00 00 03 FF 83 02
(In this case client ask for 6 registers starting with register number 900)
Possible overwork:
1. Set HMI STU communication optimization mode to : Prefered Frame lenght = Minimum possible. Vijeo Designer, Equipment configuration.
2. Upgrade AS-P to version 2.0.3.45 (solution tested in ModScan32 tool)
Released for:Schneider Electric Global

