{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
ATS22- Why can't I access all programming menus?

Article available in these languages: Czech

Issue:
Can't access more than the Conf, SET, and SUP menus on the ATS22.

Product Line:
Altistart 22

Environment:
All

Cause:
Programming

Resolution:
This is an access level issue. Set LAC= On (Conf menu), and you will have access to all programming menus.
s

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: