Issue:
ATV320 STO status on screen.
Product line:
Altivar 320
Environment:
All
Cause:
There is a circuit in the terminal block that is not closed.
Resolution:
On the terminal block, look for P24. There must be a jumper between P24-STO.
Without this jumper the drive will display STO on the screen and will not be able to run.
ATV320 STO status on screen.
Product line:
Altivar 320
Environment:
All
Cause:
There is a circuit in the terminal block that is not closed.
Resolution:
On the terminal block, look for P24. There must be a jumper between P24-STO.
Without this jumper the drive will display STO on the screen and will not be able to run.
Released for:Schneider Electric Global