Issue
When connecting to SFTP server to publish data, gives an error: "Could not parse response code. Server Reply: SSH-2.0"
Product Line
Com'X 200/210 (EBX200/210)
Com'X 500/510 (EBX500/510)
Environment
Com'X 500/200 Publishing Data to the SFTP server
Cause
In Com'X 500/200 series, SFTP is not supported for data publishing. Remote SFTP Server is expecting to use SFTP protocol and SSH connection not plain FTP.
Resolution
Four(4) supported Transfer Protocols by COM'X 500/200 series are:
For any reason if FTP Transport is the only possible option, then port 21 on remote server needs to be open.
Connection on Port 21 is for FTP and Port 22 is for SFTP/SSH.
Here are the User guides for the Com'X 500/200 series:
200/210
https://www.se.com/ww/en/download/document/DOCA0036EN/
500/510
https://www.se.com/ww/en/download/document/DOCA0098EN/
When connecting to SFTP server to publish data, gives an error: "Could not parse response code. Server Reply: SSH-2.0"
Product Line
Com'X 200/210 (EBX200/210)
Com'X 500/510 (EBX500/510)
Environment
Com'X 500/200 Publishing Data to the SFTP server
Cause
In Com'X 500/200 series, SFTP is not supported for data publishing. Remote SFTP Server is expecting to use SFTP protocol and SSH connection not plain FTP.
Resolution
Four(4) supported Transfer Protocols by COM'X 500/200 series are:
- HTTPS
- HTTP
- FTP
- SMTP
For any reason if FTP Transport is the only possible option, then port 21 on remote server needs to be open.
Connection on Port 21 is for FTP and Port 22 is for SFTP/SSH.
Here are the User guides for the Com'X 500/200 series:
200/210
https://www.se.com/ww/en/download/document/DOCA0036EN/
500/510
https://www.se.com/ww/en/download/document/DOCA0098EN/
Released for:Schneider Electric Global