How do we display values in a Textbox or Rectangle in a WebVisualization in EcoStruxure Machine Expert?

Issue
In a WebVisualization interface, how do we configure a Textbox or Rectangle to display String or Numeric values?

Product Line
EcoStruxure Machine Expert
Modicon M241, M251, and M262 PLCs

Environment
PLC Logic Builder - WebVisualization in CoDeSys engine

Resolution
In order to display Strings or Numeric values in either a Rectangle or a Text box in the Visualization,
you need to enter a Placeholder Wildcard in the "Texts-> Text" field:
"%s" for Strings
"%d" for Numeric Values

Then in the "Text variables->Text variable" property, choose a Symbol from your PLC project to display in the object.
See this example of a Text field object element:
WebVisualization

More information can be seen in the CoDeSys documentation page:
CoDeSys Visualization (3.5.17.0) ->Reference, Programming -> Placeholders with Format Definition in the Output Text

help section
help section

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Global

How do we display values in a Textbox or Rectangle in a WebVisualization in EcoStruxure Machine Expert?

Issue
In a WebVisualization interface, how do we configure a Textbox or Rectangle to display String or Numeric values?

Product Line
EcoStruxure Machine Expert
Modicon M241, M251, and M262 PLCs

Environment
PLC Logic Builder - WebVisualization in CoDeSys engine

Resolution
In order to display Strings or Numeric values in either a Rectangle or a Text box in the Visualization,
you need to enter a Placeholder Wildcard in the "Texts-> Text" field:
"%s" for Strings
"%d" for Numeric Values

Then in the "Text variables->Text variable" property, choose a Symbol from your PLC project to display in the object.
See this example of a Text field object element:
WebVisualization 

More information can be seen in the CoDeSys documentation page:
CoDeSys Visualization (3.5.17.0) ->Reference, Programming -> Placeholders with Format Definition in the Output Text

help section 
help section 

 

If this FAQ did not solve your issue, you can chat with us at  chat with us  or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Global

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.